503235
32
Zoom out
Zoom in
Previous page
1/96
Next page
Installation
32 Instruction manual ADMR
3
is
3.10.4 Connecting flue damper
1. Feed the power cable through the metric strain relief in the top of the control
column.
2. Connect earth ( ), live (L
5
) and neutral (N) to terminals 25, 26 and 27. Next
connect the three coded black wires (1 through 3) to terminals 28), lead 2
to terminal 29 (X
1
) and lead 3 to terminal 30 (X
2
). See the terminal block
connections table (3.10.2 "Preparation").
3. Turn the strain relief tight to clamp the lead.
4. If you do not need to make any more connections, fit the protective cover
onto the control column.
3.10.5 Connecting an isolating transformer
An isolating transformer should be used if there is a case of 'floating neutral'.
1. Refer to the fitting instructions provided with the isolating transformer.
(Contact the supplier for details of the correct isolating transformer.)
2. Connect the cables from the isolating transformer to terminals 31 through 36
of the terminal block as indicated in the accompanying instructions. If
necessary, consult the Electrical Diagrams ADMR
.
3. If you do not need to make any more connections, fit the protective cover
onto the control column.
3.10.6 Connecting a continuous pump
The continuous pump will start up as soon as mains power is connected to the
1. Feed the power cable through the metric strain relief in the top of the control
column.
2. Connect earth ( ), live (L
1
) and neutral (N) to terminals 7, 8 and 9 as
indicated in the terminal block connections table (3.10.2 "Preparation").
3. Turn the strain relief tight to clamp the lead.
4. If you do not need to make any more connections, fit the protective cover
onto the control column.
3.10.7 Connecting top to bottom circulation pump
The top to bottom circulation pump is program-controlled. Switching on of the
shunt pump is determined by settings of the electronic controller.
1. Feed the power cable through the metric strain relief in the top of the control
column.
2. Connect earth ( ), live (L
1
) and neutral (N) to terminals 4, 5 and 6 as
indicated in the terminal block connections table (3.10.2 "Preparation")
.
3. Turn the strain relief tight to clamp the lead.
4. If you do not need to make any more connections, fit the protective cover
onto the control column.
3.10.8 Connecting an extra ON mode switch ("Tank ON")
Tank ON is a facility for connecting an external ON/OFFswitch. In the OFF
position, the programmed operating mode is active. In the ON position, the
programmed operating mode is overruled, and "ONmode" is active.
1. Feed the power cable through the metric strain relief in the top of the control
column.
2. Connect cables (X
1
and X
2
) to terminals 13 and 14 as indicated in the
terminal block connections table (3.10.2 "Preparation")
.
3. Turn the strain relief tight to clamp the lead.
4. If you do not need to make any more connections, fit the protective cover
onto the control column.
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith ADMR80 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith ADMR80 in the language / languages: English as an attachment in your email.

The manual is 2,5 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith ADMR80

A.O. Smith ADMR80 User Manual - Dutch - 104 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info