Instruction manual ADMR 72
F06 (lock out error)
Short circuit between
flame probe and earth
Damaged cable in
contact with metal
surface.
Check the wiring of the flame probe. If necessary, replace the
wiring.
If the error persists, contact your installation engineer.
To replace the necessary parts, you must contact your installation
engineer
Ceramic part of the
flame probe is
broken/cracked.
1. Check that the ceramic part of the flame probe is still intact in
the vicinity of the burner's air distribution plate.
2. If not, the flame probe must be replaced.
F07 (lock out error)
A flame has been
detected after the gas
valve was closed.
Defective gas valves 1. Check whether there is still burner pressure present after the
gas valves have closed.
2. Check whether a flame is still present after the gas valves have
closed.
3. If this is the case, the gas control must be replaced.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
F08 (lock out error)
Error message from
safety relay
Flame detection before
the gas valve opened.
1. Reset electronic controller.
2. If the error reappears, replace the electronic controller.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
F09 (lock out error)
Water temperature
safety.
The temperature at the
top of the tank exceeds
93 °C.
1. Check that the circulation pump (if present) is working
2. Check the position of the temperature sensor T
1
.
3. Reset appliance controller
Note
Error “F09” stays active if the water temperature was higher
than 78 °C during the reset. If this is the case, first open the nearest
draw-off point to drain some hot water and allow cold water to run
into the system.
If the error cannot be resolved or is persistent, contact your
installation engineer
F10 (lock out error)
Restriction on the
number of ignition
attempts based on
switching of the flue
damper relay.
Flue damper relay
switching during
demand.
1. Check that the red arrow on the flue damper motor goes fully to
the right and stays in this position during heat demand.
2. Check for physical blockages, and rectify if possible.
3. Check that the voltage on the black lead of the motor controller
continues during heat demand.
4. Check for faulty electrical connections and rectify if possible.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
Symptom Cause Solution Remark
72


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith ADMR135 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith ADMR135 in the language / languages: English as an attachment in your email.

The manual is 2,5 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith ADMR135

A.O. Smith ADMR135 User Manual - Dutch - 104 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info